blog:katherine_temperature_humidity_sensors [2014/07/24 10:40]
Jamie McCallum
blog:katherine_temperature_humidity_sensors [2014/07/29 01:43]
Jamie McCallum
Line 14: Line 14:
  
 TrueTemp=MonicaTemp TrueTemp=MonicaTemp
 +
 +The temperature and humidity sensors in the Katherine pedestal and hub have been recalibrated using the data from the loggers (29/7/14 ~0140 UT). Data from Monica recorded before this time can be rescaled using the formulae below:
 +
 +**Pedestal:​**
 +
 +TrueRH = MonicaRH*0.95 + 23
 +
 +TrueTemp=MonicaTemp*0.92 + 0.32
 +
 +**Hub:**
 +
 +TrueRH = MonicaRH * 0.83  +27
 +
 +TrueTemp=MonicaTemp *0.93 +0.77
 +
 +**Feed**
 +
 +Feed temp & RH sensors still not working.
  